ENVIROLEX® Single Core 110°C Flexible
ENVIROLEX® Single Core 110°C Flexible
ENVIROLEX
Single core flexible copper conductor, 0.6/1kV X-HF-110 insulated, HFS-110-TP sheathed to AS/NZS 5000.1, Low smoke zero halogen insulation and sheath, 110°C continuous
Read more10mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX01AA001CXNA - Country ref. BZHX01AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 13.9 kg/100m
- Conductor cross-section: 10 mm²
- Nominal overall diameter: 8.6 mm
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Maximum Pull Tension of Conductor: 0 kN
- Maximum Pulling Tension: 0.2 kN
- Minimum Bend Radius - During Installation (under Tension): 52 mm
- Minimum Bend Radius - Installed: 34 mm
120mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE87AA001CXNA - Country ref. BZHE87AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 118.0 kg/100m
- Conductor cross-section: 120 mm²
- Nominal overall diameter: 20.4 mm
- Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
- Maximum Pull Tension of Conductor: 2 kN
- Maximum Pulling Tension: 2.4 kN
- Minimum Bend Radius - During Installation (under Tension): 120 mm
- Minimum Bend Radius - Installed: 82 mm
150mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE88AA001CXNA - Country ref. BZHE88AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 146.0 kg/100m
- Conductor cross-section: 150 mm²
- Nominal overall diameter: 22.5 mm
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
- Maximum Pull Tension of Conductor: 3 kN
- Maximum Pulling Tension: 2.7 kN
- Minimum Bend Radius - During Installation (under Tension): 140 mm
- Minimum Bend Radius - Installed: 90 mm
16mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX02AA001CXNA - Country ref. BZHX02AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 20.0 kg/100m
- Conductor cross-section: 16 mm²
- Nominal overall diameter: 9.8 mm
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Maximum Pull Tension of Conductor: 0 kN
- Maximum Pulling Tension: 0.32 kN
- Minimum Bend Radius - During Installation (under Tension): 59 mm
- Minimum Bend Radius - Installed: 39 mm
185mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE89AA001CXNA - Country ref. BZHE89AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 178.0 kg/100m
- Conductor cross-section: 185 mm²
- Nominal overall diameter: 24.8 mm
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Maximum Pull Tension of Conductor: 4 kN
- Maximum Pulling Tension: 2.98 kN
- Minimum Bend Radius - During Installation (under Tension): 150 mm
- Minimum Bend Radius - Installed: 99 mm
240mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE90AA001CXNA - Country ref. BZHE90AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 230.0 kg/100m
- Conductor cross-section: 240 mm²
- Nominal overall diameter: 27.9 mm
- Max. DC resistance of the conductor at 20°C: 0.0801 Ohm/km
- Maximum Pull Tension of Conductor: 5 kN
- Maximum Pulling Tension: 3.35 kN
- Minimum Bend Radius - During Installation (under Tension): 250 mm
- Minimum Bend Radius - Installed: 167 mm
25mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX03AA001CXNA - Country ref. BZHX03AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 28.9 kg/100m
- Conductor cross-section: 25 mm²
- Nominal overall diameter: 11.3 mm
- Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
- Maximum Pull Tension of Conductor: 0 kN
- Maximum Pulling Tension: 0.5 kN
- Minimum Bend Radius - During Installation (under Tension): 70 mm
- Minimum Bend Radius - Installed: 45 mm
300mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE91AA001CXNA - Country ref. BZHE91AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 285.0 kg/100m
- Conductor cross-section: 300 mm²
- Nominal overall diameter: 30.8 mm
- Max. DC resistance of the conductor at 20°C: 0.0641 Ohm/km
- Maximum Pull Tension of Conductor: 6 kN
- Maximum Pulling Tension: 3.7 kN
- Minimum Bend Radius - During Installation (under Tension): 280 mm
- Minimum Bend Radius - Installed: 185 mm
35mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX04AA001CXNA - Country ref. BZHX04AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 37.7 kg/100m
- Conductor cross-section: 35 mm²
- Nominal overall diameter: 12.5 mm
- Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
- Maximum Pull Tension of Conductor: 1 kN
- Maximum Pulling Tension: 0.7 kN
- Minimum Bend Radius - During Installation (under Tension): 80 mm
- Minimum Bend Radius - Installed: 50 mm
400mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE92AA001CXNA - Country ref. BZHE92AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 370.0 kg/100m
- Conductor cross-section: 400 mm²
- Nominal overall diameter: 34.7 mm
- Max. DC resistance of the conductor at 20°C: 0.0486 Ohm/km
- Maximum Pull Tension of Conductor: 8 kN
- Maximum Pulling Tension: 4.16 kN
- Minimum Bend Radius - During Installation (under Tension): 310 mm
- Minimum Bend Radius - Installed: 208 mm
500mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE93AA001CXNA - Country ref. BZHE93AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 471.0 kg/100m
- Conductor cross-section: 500 mm²
- Nominal overall diameter: 40.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0384 Ohm/km
- Maximum Pull Tension of Conductor: 10 kN
- Maximum Pulling Tension: 4.8 kN
- Minimum Bend Radius - During Installation (under Tension): 360 mm
- Minimum Bend Radius - Installed: 240 mm
50mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX05AA001CXNA - Country ref. BZHX05AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 53.2 kg/100m
- Conductor cross-section: 50 mm²
- Nominal overall diameter: 14.3 mm
- Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
- Maximum Pull Tension of Conductor: 1 kN
- Maximum Pulling Tension: 1 kN
- Minimum Bend Radius - During Installation (under Tension): 90 mm
- Minimum Bend Radius - Installed: 57 mm
630mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHE94AA001CXNA - Country ref. BZHE94AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 630.0 kg/100m
- Conductor cross-section: 630 mm²
- Nominal overall diameter: 44.6 mm
- Max. DC resistance of the conductor at 20°C: 0.0287 Ohm/km
- Maximum Pull Tension of Conductor: 13 kN
- Maximum Pulling Tension: 5.35 kN
- Minimum Bend Radius - During Installation (under Tension): 400 mm
- Minimum Bend Radius - Installed: 268 mm
70mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX63AA001CXNA - Country ref. BZHX63AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 74.9 kg/100m
- Conductor cross-section: 70 mm²
- Nominal overall diameter: 16.2 mm
- Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
- Maximum Pull Tension of Conductor: 1 kN
- Maximum Pulling Tension: 1.4 kN
- Minimum Bend Radius - During Installation (under Tension): 100 mm
- Minimum Bend Radius - Installed: 65 mm
95mm2 Cu Flexible Envirolex 110C
Nexans ref. BZHX64AA001CXNA - Country ref. BZHX64AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 100.0 kg/100m
- Conductor cross-section: 95 mm²
- Nominal overall diameter: 18.1 mm
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Maximum Pull Tension of Conductor: 2 kN
- Maximum Pulling Tension: 1.9 kN
- Minimum Bend Radius - During Installation (under Tension): 110 mm
- Minimum Bend Radius - Installed: 72 mm
Description
Description
Standards
-
ProductAS/NZS 5000.1
-
TestAS/NZS 4507; IEC 60332-3 Cat.A
ENVIROLEX® flexible single core cable is part of the Nexans Fire Safety Offer. As a Low Fire Hazard (LFH) range, ENVIROLEX® is PVC-free, made with flame retardant compound and reduces toxic smoke emissions in the event of fire, allowing time for safe evacuation.
Application
- 0.6/1kV cables,
- Flexible, X-HF-110 insulated to AS/NZS 5000.1
- HFS-110-TP sheathed to AS/NZS 5000.1
- 110°C continuous
- Low fire hazard - Flame retardant
- PVC-free
- Meets physical property requirements of 125°C XLPO insulation to UL 1581
*Also known as ENVIROLEX® Single Core
110; Flexible; LS0H, LSZH; LFH; Envirolex; Green Star; Mains; Sub Mains; Flame Retardant
RHE-3 to AS/NZ 4507. IEC60332-3 Cat A Bunched Flame Propagation.
Suitable for public buildings and infrastructure projects.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
ENVIROLEX® Flexible Single Core 110°C - Current carrying capacity table single phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110
Maximum conductor temperature: 110°C
Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 26 | 26 | 21 | 21 | 16 | 10 | 33 | 24 | 27 |
1.5 | 32 | 32 | 26 | 25 | 20 | 13 | 40 | 30 | 34 |
2.5 | 43 | 42 | 34 | 33 | 27 | 17 | 53 | 39 | 44 |
4.0 | 57 | 56 | 45 | 45 | 36 | 23 | 69 | 51 | 57 |
6.0 | 73 | 70 | 57 | 56 | 45 | 29 | 86 | 64 | 71 |
10.0 | 102 | 98 | 80 | 77 | 51 | 40 | 117 | 86 | 96 |
16.0 | 135 | 129 | 105 | 102 | 82 | 53 | 151 | 112 | 125 |
25.0 | 178 | 170 | 139 | 133 | 106 | 70 | 192 | 143 | 158 |
35.0 | 221 | 210 | 172 | 167 | 133 | 86 | 232 | 176 | 195 |
50.0 | 279 | 263 | 218 | 207 | 165 | 0 | 284 | 215 | 237 |
70.0 | 351 | 329 | 273 | 263 | 210 | 0 | 345 | 266 | 287 |
95.0 | 422 | 395 | 329 | 312 | 250 | 0 | 403 | 312 | 341 |
120.0 | 500 | 466 | 390 | 364 | 291 | 0 | 464 | 359 | 392 |
150.0 | 577 | 536 | 450 | 426 | 341 | 0 | 524 | 414 | 451 |
185.0 | 660 | 611 | 516 | 481 | 385 | 0 | 585 | 464 | 503 |
240.0 | 794 | 732 | 621 | 583 | 467 | 0 | 682 | 548 | 599 |
300.0 | 916 | 841 | 716 | 0 | 0 | 0 | 769 | 631 | 675 |
400.0 | 1105 | 1006 | 860 | 0 | 0 | 0 | 893 | 734 | 784 |
500.0 | 1290 | 1164 | 999 | 0 | 0 | 0 | 1009 | 855 | 909 |
630.0 | 1529 | 1359 | 1168 | 0 | 0 | 0 | 1154 | 977 | 1046 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |
ENVIROLEX® Flexible Single Core 110°C - Current carrying capacity table three phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110
Maximum conductor temperature: 110°C
Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 25 | 22 | 21 | 18 | 15 | 10 | 28 | 21 | 25 |
1.5 | 31 | 27 | 26 | 23 | 19 | 13 | 35 | 26 | 31 |
2.5 | 42 | 36 | 34 | 31 | 24 | 17 | 46 | 34 | 40 |
4.0 | 55 | 48 | 45 | 40 | 32 | 23 | 59 | 44 | 52 |
6.0 | 70 | 61 | 57 | 50 | 40 | 29 | 74 | 55 | 65 |
10.0 | 99 | 85 | 80 | 70 | 56 | 40 | 99 | 76 | 87 |
16.0 | 130 | 112 | 105 | 91 | 73 | 53 | 127 | 97 | 113 |
25.0 | 173 | 149 | 139 | 121 | 97 | 70 | 162 | 125 | 143 |
35.0 | 214 | 184 | 172 | 148 | 118 | 86 | 196 | 151 | 176 |
50.0 | 270 | 233 | 217 | 190 | 152 | 0 | 238 | 188 | 213 |
70.0 | 340 | 292 | 273 | 234 | 187 | 0 | 290 | 229 | 257 |
95.0 | 410 | 353 | 329 | 277 | 221 | 0 | 338 | 268 | 306 |
120.0 | 487 | 418 | 390 | 331 | 265 | 0 | 388 | 316 | 350 |
150.0 | 562 | 482 | 450 | 378 | 302 | 0 | 438 | 357 | 403 |
185.0 | 644 | 553 | 516 | 438 | 350 | 0 | 489 | 404 | 448 |
240.0 | 775 | 665 | 620 | 538 | 430 | 0 | 569 | 481 | 534 |
300.0 | 895 | 766 | 714 | 612 | 489 | 0 | 641 | 542 | 600 |
400.0 | 1079 | 918 | 855 | 757 | 606 | 0 | 742 | 648 | 693 |
500.0 | 1260 | 1064 | 990 | 864 | 691 | 0 | 835 | 729 | 803 |
630.0 | 1493 | 1240 | 1154 | 993 | 794 | 0 | 950 | 828 | 918 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |
Selling & delivery Information
Nexans Fire Safety Offer ENVIROLEX® Low Fire Hazard Cables PVC-free Red List Free and Declare Labelled Green Star Flexible conductor
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania