VERSOLEX 110 4x2.5mm2+E Black
VERSOLEX 110 4x2.5mm2+E Black
VERSOLEX
VERSOLEX 110 4x2.5mm2+E Black
Read more- Nexans ref. : HTSR05AA004CXAA
Description
Description
Standards
-
ProductAS/NZS 5000.1
- Class 5 & 6 flexible copper conductor
- 0.6/1kV cables to AS/NZS5000.1,
- X-HF-110 insulated
- TPE sheathed,
- Submersible up to 500m
- Maximum operating temperature 110°C
- PVC components meet Best Practice Guidelines for PVC in the built environment.
Also available in Low Smoke Zero Halogen materials. See Envirolex under "Low Fire Hazard".
In systems intended to operate continuously at 110°C maximum operating temperature, Nexans Envirolex - Low Fire Hazard is recommended. Note that designing and operating a system continuously at maximum operating temperature is unlikely to be energy efficient over the life of the asset.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Insulation colour
Red, White, Blue, Black, Green/Yellow
Outer sheath
TPE
Sheath colour
Black
Type of conductor
Stranded flexible
With Green/Yellow core
Yes
Dimensional characteristics
Dimensional characteristics
Approximate weight
24.0 kg/100m
Conductor cross-section
2.5 mm²
Maximum diameter of wires
0.26 mm
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
13.1 mm
Number of cores
4
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
10.2 Ohm/km
Inductive resistance at 50Hz
0.1 Ohm/km
Insulation resistance at 20°C
950 MOhm.km
Max. DC resistance of the conductor at 20°C
7.98 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Maximum Pulling Tension
0.6 kN
Usage characteristics
Usage characteristics
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
78.6 mm
Minimum Bend Radius - Installed
52.4 mm