1X240mm2 Versolex Orange

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • 0.6/1kV cables,
  • Flexible X-90 (XLPE) insulated
  • TPE sheathed to AS/NZS 5000.1 (Power),
  • Copper conductors, 90°C.
  • Submersible up to 500m

 

Also available in Low Smoke Zero Halogen materials at 110°C. See Alsecure Envirolex under "Fire Performance".

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Orange
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-90
Outer sheath
TPE
Type of conductor
Stranded flexible
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
241.0 kg/100m
Cable length
- m
Conductor cross-section
240 mm²
Conductor diameter
21.0 mm
Diameter over insulation
24.4 mm
Maximum diameter of wires
0.51 mm
Neutral conductor section (when smaller)
- mm²
Nominal overall diameter
27.9 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
0.105 Ohm/km
Inductive reactance at 50Hz - flat touching
0.099 Ohm/km
Inductive reactance at 50Hz - trefoil
0.084 Ohm/km
Insulation resistance at 20°C
330 MOhm.km
Max. DC resistance of the conductor at 20°C
0.08 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Maximum Pull Tension of Conductor
5 kN

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Minimum Bend Radius - During Installation (under Tension)
251 mm
Minimum Bend Radius - Installed
167 mm

Resources

Resources

Versolex Single Core - Current carrying capacity table single phase (in Amps)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
240.0 668.0 613.0 515.0 452.0 361.0 0.0 616.0 486.0 523.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual Wiring Enclosure

Versolex Single Core - Current carrying capacity table three phase (in Amps)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
240.0 651.0 553.0 514.0 391.0 313.0 0.0 511.0 416.0 465.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual Wiring Enclosure

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close