VERSOLEX 110 Flexible 10mm2 Cu Black
VERSOLEX 110 Flexible 10mm2 Cu Black
VERSOLEX
VERSOLEX 110 Flexible 10mm2 Cu Black
Read more- Nexans ref. : BESX01AA001CXNA
Description
Description
Standards
-
ProductAS/NZS 5000.1
- 0.6/1kV cables,
- Flexible X-HF-110 insulated to AS/NZS5000.1
- TPE sheathed
- Copper flexible conductors.
- Submersible up to 500m
- Maximum operating temperature 110°C
- PVC components meet Best Practice Guidelines for PVC in the built environment.
Also available in Low Smoke Zero Halogen (low fire hazard). See Envirolex - Low Fire Hazard
In systems intended to operate continuously at 110°C maximum operating temperature, Nexans Envirolex - Low Fire Hazard is recommended. Note that designing and operating a system continuously at maximum operating temperature is unlikely to be energy efficient over the life of the asset
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Outer sheath
TPE
Type of conductor
Copper
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
14.0 kg/100m
Cable length
- m
Conductor cross-section
10 mm²
Maximum diameter of wires
0.21 mm
Neutral conductor section (when smaller)
- mm²
Nominal overall diameter
8.6 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
2.59 Ohm/km
Inductive reactance at 50Hz - flat touching
0.123 Ohm/km
Inductive reactance at 50Hz - trefoil
0.107 Ohm/km
Insulation resistance at 20°C
370 MOhm.km
Max. DC resistance of the conductor at 20°C
1.91 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Maximum Pulling Tension
0.2 kN
Usage characteristics
Usage characteristics
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
52 mm
Minimum Bend Radius - Installed
34 mm
Resources
Resources
VERSOLEX® 110 Flexible Single Core 110°C - Current carrying capacity table three phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110 Maximum conductor temperature: 110°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUNDConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 99.0 | 85.0 | 80.0 | 70.0 | 56.0 | 40.0 | 99.0 | 76.0 | 87.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |
VERSOLEX® 110 Flexible Single Core 110°C - Current carrying capacity table single phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110 Maximum conductor temperature: 110°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUNDConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 102.0 | 98.0 | 80.0 | 77.0 | 51.0 | 40.0 | 117.0 | 86.0 | 96.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania