- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
1X95mm2 Versolex Orange
Description
Description
Standards
-
ProductAS/NZS 5000.1
- 0.6/1kV cables,
- Flexible X-90 (XLPE) insulated
- TPE sheathed to AS/NZS 5000.1 (Power),
- Copper conductors, 90°C.
- Submersible up to 500m
Also available in Low Smoke Zero Halogen materials at 110°C. See Alsecure Envirolex under "Fire Performance".
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Orange
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-90
Outer sheath
TPE
Type of conductor
Stranded flexible
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
98.7 kg/100m
Cable length
- m
Conductor cross-section
95 mm²
Conductor diameter
12.8 mm
Diameter over insulation
15.0 mm
Maximum diameter of wires
0.51 mm
Neutral conductor section (when smaller)
- mm²
Nominal overall diameter
18.1 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.264 Ohm/km
Inductive reactance at 50Hz - flat touching
0.104 Ohm/km
Inductive reactance at 50Hz - trefoil
0.088 Ohm/km
Insulation resistance at 20°C
340 MOhm.km
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Maximum Pull Tension of Conductor
2 kN
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Minimum Bend Radius - During Installation (under Tension)
109 mm
Minimum Bend Radius - Installed
72 mm
Resources
Resources
Versolex Single Core - Current carrying capacity table single phase (in Amps)
Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUNDConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
95.0 | 351.0 | 328.0 | 271.0 | 248.0 | 198.0 | 0.0 | 364.0 | 276.0 | 299.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual Wiring Enclosure |
Versolex Single Core - Current carrying capacity table three phase (in Amps)
Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUNDConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
95.0 | 341.0 | 290.0 | 271.0 | 214.0 | 171.0 | 0.0 | 304.0 | 237.0 | 268.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual Wiring Enclosure |