1x500mm2 Versolex Orange

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • 0.6/1kV cables,
  • Flexible X-90 (XLPE) insulated
  • TPE sheathed to AS/NZS 5000.1 (Power),
  • Copper conductors, 90°C.
  • Submersible up to 500m

 

Also available in Low Smoke Zero Halogen materials at 110°C. See Alsecure Envirolex under "Fire Performance".

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Orange
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-90
Outer sheath
TPE
Type of conductor
Stranded flexible
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
500.0 kg/100m
Cable length
- m
Conductor cross-section
500 mm²
Conductor diameter
31.5 mm
Diameter over insulation
36.0 mm
Maximum diameter of wires
0.51 mm
Neutral conductor section (when smaller)
- mm²
Nominal overall diameter
40.0 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
0.055 Ohm/km
Inductive reactance at 50Hz - flat touching
0.096 Ohm/km
Inductive reactance at 50Hz - trefoil
0.08 Ohm/km
Insulation resistance at 20°C
280 MOhm.km
Max. DC resistance of the conductor at 20°C
0.038 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Maximum Pull Tension of Conductor
10 kN

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Minimum Bend Radius - During Installation (under Tension)
360 mm
Minimum Bend Radius - Installed
240 mm

Resources

Resources

Versolex Single Core - Current carrying capacity table single phase (in Amps)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
500.0 1090.0 975.0 830.0 0.0 0.0 0.0 906.0 733.0 812.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual Wiring Enclosure

Versolex Single Core - Current carrying capacity table three phase (in Amps)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 OR R-CSP-90 Maximum conductor temperature: 90°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
500.0 1062.0 884.0 821.0 630.0 504.0 0.0 746.0 642.0 717.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual Wiring Enclosure

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close