4C+E 4mm2 Cu Flexible Envirolex

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • Test
    AS/NZS 4507; IEC 60332-3 Cat.C

ENVIROLEX® flexible multicore cable is part of the Nexans Fire Safety Offer. As a Low Fire Hazard (LFH) range, ENVIROLEX® is PVC-free, made with flame retardant compound and reduces toxic smoke emissions in the event of fire, allowing time for safe evacuation.

Design

  • Class 5 & 6 flexible conductor
  • 0.6/1kV cables,
  • Flexible, X-HF-110 insulated
  • HFS-110-TP sheathed to AS/NZS 5000.1 (Power), copper conductors),
  • 110°C continuous, Low smoke - zero halogen.
  • Low Fire Hazard cable
  • PVC-free
  • Meets physical property requirements of 125°C XLPO insulation to UL 1581

110; Flexible; LS0H; LFH; Envirolex; Mains; Sub Mains; Flame Retardant

Reduced fire hazard - ideal for public buidlings and infrastructure projects where reduce flame propagation is a priority.

RHE-3 to AS/NZS 4507

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Black
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Insulation colour
Red, White, Blue, Black, Green/Yellow
Outer sheath
HFS-110-TP
Type of conductor
Stranded flexible
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Approximate weight
30.6 kg/100m
Conductor cross-section
4 mm²
Conductor diameter
2.6 mm
Diameter over insulation
4.0 mm
Earth conductor cross section
2.5 mm²
Maximum diameter of wires
0.31 mm
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
14.2 mm
Number of cores
4
Number of earth cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
6.7 Ohm/km
Inductive reactance at 50Hz
0.091 Ohm/km
Insulation resistance at 20°C
1280 MOhm.km
Max. DC resistance of the conductor at 20°C
4.95 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Maximum Pulling Tension
0.32 kN

Usage characteristics

Usage characteristics

Fire safety
-
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
85 mm
Minimum Bend Radius - Installed
55 mm

Resources

Resources

Selling & delivery Information

Nexans Fire Safety Offer ENVIROLEX® Low Fire Hazard Cables PVC-free Red List Free and Declare Labelled Green Star Flexible conductor

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close