16mm2 Cu 0.6/1.0kV Flexible Alsecure Plus 110C

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • Installation
    AS/NZS 3013
  • Test
    AS/NZS 4507; IEC 60332-3 Cat.A

Construction:
Stranded Flexible (Class 5) Plain Annealed Copper Conductor, Mica Taped,
X-HF-110 Insulated, HFS-110-TP Sheathed to AS/NZS 5000.1, 110°C, WS52W Fire Rated to AS/NZS 3013.

ALSECURE® Single Core cables are a range of Fire Rated single core products for use in mains and sub-mains applications.
Rated to 0.6/1kV, 110°C, this Low Fire Hazard (LSZH/LS0H) range of Fire Resistant cables will maintain circuit integrity and life-saving essential services in the event of fire. The ALSECURE® Single Core range is readily available in sizes from 10mm² to 630mm².

Features

  • Flexible stranded copper conductor
  • Halogen free, low smoke and low corrosive/acid emissions, & flame retardant materials
  • 110ºC rated insulation and sheath
  • WS52W Rated to AS/NZS 3013
  • Cat A bunched flame propagation to IEC 60332-3
  • RHE-3 to AS/NZS 4507
  • Meets physical property requirements of 125°C XLPO insulation to UL 1581

Benefits

  • Flexibility for fast, easy installation
  • Contributes to the green star rating of your project
  • Safer evacuation and better protection for essential building systems

The Alsecure Plus product range is suitable for Green Star Buildings as they do not contain any PVC.

Applications

  • Fire resistant Power Circuit
  • Consumer mains and Subs Mains
  • Lift sub mains
  • Power Cable to fire pumps and essential circuits

Voltage
0.6 / 1 KV

Continuous Operating Temperature
110°C

Colours
Insulation - White(Natural)
Outer Sheath - RED

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Red
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Outer sheath
HFS-110-TP
Type of conductor
Stranded flexible

Dimensional characteristics

Dimensional characteristics

Approximate weight
22.3 kg/100m
Conductor cross-section
16 mm²
Conductor diameter
5.3 mm
Diameter over insulation
8.0 mm
Nominal insulation thickness
0.8 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
10.8 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
1.64 Ohm/km
Inductive reactance at 50Hz - flat touching
0.116 Ohm/km
Inductive reactance at 50Hz - trefoil
0.101 Ohm/km
Insulation resistance at 20°C
340 MOhm.km
Max. DC resistance of the conductor at 20°C
1.21 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Maximum Pull Tension of Conductor
0 kN
Maximum Pulling Tension
0.32 kN

Usage characteristics

Usage characteristics

Fire safety
-
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
97 mm
Minimum Bend Radius - Installed
65 mm

Resources

Resources

Alsecure Plus single core - Current carrying capacity table single phase (in Amps)

Flexible Copper Conductor Insulation X-HF-110 Maximum Conductor Temperature 110⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
16.0 135.0 129.0 105.0 102.0 82.0 53.0 151.0 112.0 125.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual wiring enclosure

Alsecure Plus single core - Current carrying capacity table three phase (in Amps)

Flexible Copper Conductor Insulation X-HF-110 Maximum Conductor Temperature 110⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
16.0 130.0 112.0 105.0 91.0 73.0 53.0 127.0 97.0 113.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual wiring enclosure

Selling & delivery Information

Nexans Fire Safety Offer ALSECURE® Fire Resistant Cables PVC-free Red List Free and Declare Labelled

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error