- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
3C 240mm2 Cu 6.35/11kV PVC Black
3C 240mm2 Cu 6.35/11kV PVC Black
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHP26AA003CXAA
- Country ref. : XJHP26AA003CXAA
- EAN : 99319215217009
Description
Description
Standards
-
InternationalIEC 60228; IEC 60502-2
-
NationalAS/NZS 1125; AS/NZS 1429.1
Construction
- Stranded compacted conductors
- Semi-conductive insulation screen
- Copper wire screen
- XLPE insulation
- Semi-conductive conductor screen
- PVC sheath
- Fillers
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
965.0 kg/100m
Conductor cross-section
240 mm²
Conductor diameter
18.53 mm
Diameter over insulation
26.49 mm
Diameter over screen
29.79 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
71.6 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.098 Ohm/km
Capacitance (All Main Cores - Screen)
0.456 µF / km
Charging current per phase
0.909 A/km
DC Resistance of the Screen at 20°C
0.27 Ohm/km
Dielectric loss per phase
23.1 W/km
Inductive reactance at 50Hz
0.093 Ohm/km
Insulation resistance at 20°C
5300 MOhm.km
Max. DC resistance of the conductor at 20°C
0.075 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
34.3 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
6.35 / 11 kV
Zero sequence reactance at 50HZ
0.045 Ohm/km
Zero sequence resistance at 20°C
0.875 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
50.4 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1290 mm
Minimum Bend Radius - Installed
860 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three CoreConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
240.0 | 519.0 | 403.0 | 563.0 | 436.0 | 389.0 | 292.0 | 497.0 | 387.0 | 416.0 | 316.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground direct buried (3 core) |
Underground ducts (3 core) |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania