3C 70mm2 Al 6.35/11kV PVC Black
3C 70mm2 Al 6.35/11kV PVC Black
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHA20AA003CXAA
Description
Description
Standards
-
InternationalIEC 60228; IEC 60502-2
-
NationalAS/NZS 1125; AS/NZS 1429.1
Construction
- Stranded compacted conductors
- Semi-conductive insulation screen
- Copper wire screen
- XLPE insulation
- Semi-conductive conductor screen
- PVC sheath
- Fillers
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
245.0 kg/100m
Conductor cross-section
70 mm²
Conductor diameter
9.65 mm
Diameter over insulation
17.61 mm
Diameter over screen
20.91 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
45.96 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
51.1 mm
Number of screen wires (nb x mm Ø)
27 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.569 Ohm/km
Capacitance (All Main Cores - Screen)
0.276 µF / km
Charging current per phase
0.551 A/km
DC Resistance of the Screen at 20°C
0.39 Ohm/km
Dielectric loss per phase
14 W/km
Inductive reactance at 50Hz
0.112 Ohm/km
Insulation resistance at 20°C
8700 MOhm.km
Max. DC resistance of the conductor at 20°C
0.443 Ohm/km
Maximum electric stress
2.4 kV/mm
Permissible short circuit current conductor 1s
6.6 kA
Permissible short circuit current screen 1s
6.82 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.063 Ohm/km
Zero sequence resistance at 20°C
1.62 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
10.5 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
920 mm
Minimum Bend Radius - Installed
610 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three CoreConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
70.0 | 241.0 | 187.0 | 259.0 | 201.0 | 178.0 | 138.0 | 249.0 | 193.0 | 199.0 | 154.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground direct buried (3 core) |
Underground ducts (3 core) |
Our websites