- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
3.8/6.6kV Three Core
3.8/6.6kV Three Core
3.8.6.6kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XHHP20AA003OMAA
- Country ref. : XHHP20AA003OMAA
- EAN : 9319215507732
Description
Description
Standards
-
InternationalIEC 60228; IEC 60502-2
-
NationalAS/NZS 1125; AS/NZS 1429.1
Construction
- Stranded compacted conductor
- Semi-conductive insulation screen
- Copper wire screen
- XLPE insulation
- Semi-conductive conductor screen
- PVC sheath
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
360.0 kg/100m
Conductor cross-section
70 mm²
Conductor diameter
9.6 mm
Diameter over insulation
15.727 mm
Diameter over screen
19.027 mm
Nominal Duct Diameter
65 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
2.5 mm
Nominal overall diameter
46.7 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.342 Ohm/km
Capacitance (All Main Cores - Screen)
0.352 µF / km
Charging current per phase
0.42 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
6.39 W/km
Inductive reactance at 50Hz
0.099 Ohm/km
Insulation resistance at 20°C
6900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.268 Ohm/km
Maximum electric stress
1.8 kV/mm
Permissible short circuit current conductor 1s
10 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.039 Ohm/km
Zero sequence resistance at 20°C
1.063 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
14.7 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
840 mm
Minimum Bend Radius - Installed
560 mm
Resources
Resources
Current carrying capacity table (in Amps) - 3.8/6.6kV Three Core
Current carrying capacity table (in Amps) - 3.8/6.6kV Three CoreConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
70.0 | 238.0 | 185.0 | 256.0 | 199.0 | 173.0 | 134.0 | 249.0 | 193.0 | 195.0 | 151.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Direct Buried (3 core) |
Underground ducts (3 core) |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania