3C 185mm2 Al 12.7/22kV Three Core PVC/HDPE URD to Powercor Spec

Description

Description

Standards

  • International
    IEC 60228; IEC 60502-2
  • National
    AS/NZS 1125; AS/NZS 1429.1

Stranded compacted aluminium conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, PVC/HDPE sheathed.

XLMA - 3kA fault level

XLNA - up to 10kA fault level as standard

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC/HDPE
Screen
Copper wire
Type of conductor
Stranded compacted

Dimensional characteristics

Dimensional characteristics

Approximate weight
485.0 kg/100m
Conductor cross-section
185 mm²
Conductor diameter
15.67 mm
Diameter over insulation
27.943 mm
Diameter over screen
31.243 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
5.5 mm
Nominal overall diameter
74.9 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø

Electrical characteristics

Electrical characteristics

A.C. Conductor resist. 50Hz and at 90 °C
0.211 Ohm/km
Capacitance (All Main Cores - Screen)
0.269 µF / km
Charging current per phase
1.073 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
54.5 W/km
Inductive reactance at 50Hz
0.106 Ohm/km
Insulation resistance at 20°C
9000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
Maximum electric stress
3 kV/mm
Permissible short circuit current conductor 1s
17.5 kA
Rated Voltage Uo/U (Um)
12.7/22 kV
Screen fault current carrying capacity for 1 second
10.098 kA
Zero sequence reactance at 50HZ
0.059 Ohm/km
Zero sequence resistance at 20°C
0.961 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
27.75 kN

Usage characteristics

Usage characteristics

Minimum Bend Radius - During Installation (under Tension)
1870 mm
Minimum Bend Radius - Installed
1120 mm

Resources

Resources

Current carrying capacity table (in Amps) - 12.7/22kV Three Core URD

Current carrying capacity table (in Amps) - 12.7/22kV Three Core URD
Conductor cross-section
mm² Al Al Al Al Al
185.0 350.0 378.0 336.0 264.0 283.0
In air touching (3 core)
In air spaced from surface (3 core)
In air enclosed (3 core)
Underground Direct Buried (3 core)
Underground ducts (3 core)

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close