XLP 1X16 PC XLPPVC 1000M
XLP 1X16 PC XLPPVC 1000M
16mm2 XLPE / PVC SDI Black 1000m
Read more- Nexans ref. : BDBP15A9001CXNA
- Country ref. : BDBP15A9001CXNA
- EAN : 9319215478438
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Copper conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Copper
Type of conductor
Stranded copper
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
21.0 kg/100m
Cable length
1000 m
Conductor cross-section
16 mm²
Nominal insulation thickness
0.8 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
9.3 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.236 Ohm/km
Inductive reactance at 50Hz - flat touching
0.102 Ohm/km
Inductive reactance at 50Hz - trefoil
0.087 Ohm/km
Insulation resistance at 20°C
370 MOhm.km
Max. DC resistance of the conductor at 20°C
1.15 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
1 kN
Maximum Pulling Tension
1.1 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
56 mm
Minimum Bend Radius - Installed
37 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 112.0 | 87.0 | 108.0 | 84.0 | 86.0 | 67.0 | 84.0 | 65.0 | 67.0 | 52.0 | 43.0 | 33.0 | 139.0 | 107.0 | 100.0 | 78.0 | 112.0 | 87.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 108.0 | 84.0 | 92.0 | 71.0 | 86.0 | 67.0 | 72.0 | 56.0 | 58.0 | 45.0 | 43.0 | 33.0 | 117.0 | 91.0 | 86.0 | 66.0 | 101.0 | 79.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania