- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
XLP 1X70 PC 0.6/1KV PVC
XLP 1X70 PC 0.6/1KV PVC
70mm2 XLPE / PVC SDI Black
Read more- Nexans ref. : BDBC20AA001CXNA
- Country ref. : BDBC20AA001CXNA
- EAN : 99319215277270
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Copper conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Copper
Type of conductor
Compact copper
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
73.0 kg/100m
Cable length
- m
Conductor cross-section
70 mm²
Nominal insulation thickness
1.1 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
14.7 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.471 Ohm/km
Inductive reactance at 50Hz - flat touching
0.108 Ohm/km
Inductive reactance at 50Hz - trefoil
0.092 Ohm/km
Insulation resistance at 20°C
270 MOhm.km
Max. DC resistance of the conductor at 20°C
0.268 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
5 kN
Maximum Pulling Tension
1.8 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
180 mm
Minimum Bend Radius - Installed
120 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
70.0 | 291.0 | 226.0 | 273.0 | 212.0 | 224.0 | 174.0 | 204.0 | 159.0 | 164.0 | 127.0 | 0.0 | 0.0 | 313.0 | 243.0 | 233.0 | 181.0 | 258.0 | 200.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
70.0 | 282.0 | 219.0 | 240.0 | 186.0 | 224.0 | 174.0 | 183.0 | 142.0 | 146.0 | 114.0 | 0.0 | 0.0 | 262.0 | 203.0 | 203.0 | 158.0 | 232.0 | 180.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania