XLP 1X35 PC 0.6/1.0kV PVC 500m
XLP 1X35 PC 0.6/1.0kV PVC 500m
35mm2 XLPE / PVC SDI Black 500m
Read more- Nexans ref. : BDBC18A5001CXNA
- Country ref. : BDBC18A5001CXNA
- EAN : 9319215309237
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Copper conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Copper
Type of conductor
Compact copper
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
40.0 kg/100m
Cable length
500 m
Conductor cross-section
35 mm²
Nominal insulation thickness
0.9 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
11.5 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.884 Ohm/km
Inductive reactance at 50Hz - flat touching
0.118 Ohm/km
Inductive reactance at 50Hz - trefoil
0.102 Ohm/km
Insulation resistance at 20°C
300 MOhm.km
Max. DC resistance of the conductor at 20°C
0.524 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
2 kN
Maximum Pulling Tension
1.4 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
140 mm
Minimum Bend Radius - Installed
92 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 186.0 | 144.0 | 177.0 | 137.0 | 144.0 | 111.0 | 135.0 | 105.0 | 108.0 | 84.0 | 72.0 | 56.0 | 215.0 | 167.0 | 157.0 | 122.0 | 175.0 | 136.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 180.0 | 140.0 | 154.0 | 119.0 | 144.0 | 111.0 | 120.0 | 93.0 | 96.0 | 75.0 | 72.0 | 56.0 | 180.0 | 140.0 | 137.0 | 106.0 | 158.0 | 122.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |