4 Core + Earth 1.5mm2 0.6/1.0kV Alsecure Plus Multicore

Description

Description

Standards

  • Product
    AS/NZS 5000.1
  • Installation
    AS/NZS 3013
  • Test
    AS/NZS 4507; IEC 60332-3 Cat.A

Construction Stranded (Class 2) Copper Conductor, Mica Taped, X-HF-110 Insulated, HFS-110-TP Sheathed to AS/NZS 5000.1, 110ºC , WS52W Fire Rated to AS/NZS 3013.

Alsecure® Plus Multicore range of Fire Rated cable will maintain circuit integrity and life-saving essential services such as emergency and exit lighting, pumps and fans in the event of a fire.

Other sizes and configurations are available on request subject to minimum order quantities.

Features

  • Stranded copper conductor
  • Halogen free, low smoke, low toxic and corrosive emissions, and flame retardant materials
  • 110ºC rated insulation and sheath
  • WS52W Fire Rated to AS/NZS 3013

Benefits

  • Contributes to the green star rating of your project
  • Safer evacuation and protection of essential safety systems

 

The Alsecure Plus product range is suitable for Green Star Buildings as they do not contain any PVC.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Red
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Insulation colour
Red, White, Blue, Black, Green/Yellow
Outer sheath
HFS-110-TP
Type of conductor
Stranded
With Green/Yellow core
Yes

Dimensional characteristics

Dimensional characteristics

Approximate weight
29.1 kg/100m
Conductor cross-section
1.5 mm²
Conductor diameter
1.5 mm
Earth conductor cross section
1.5 mm²
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.8 mm
Nominal overall diameter
16.2 mm
Number of cores
5
Number of earth cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
18.4 Ohm/km
Inductive reactance at 50Hz
0.107 Ohm/km
Insulation resistance at 20°C
565 MOhm.km
Max. DC resistance of the conductor at 20°C
13.573 Ohm/km
Rated Voltage Uo/U (Um)

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Maximum Pulling Tension
0.53 kN

Usage characteristics

Usage characteristics

Fire resistant
-
Fire safety
-
Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
194 mm
Minimum Bend Radius - Installed
130 mm

Resources

Resources

Alsecure Plus Multicore - Current carrying capacity table single phase (in Amps)

Flexible Copper Conductor (>6mm2), Fixed Copper (≤10mm2) Insulation X-HF-110
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
1.5 29.0 28.0 24.0 19.0 14.0 37.0 28.0
Unenclosed spaced
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure

Alsecure Plus Multicore - Current carrying capacity table three phase (in Amps)

Flexible Copper Conductor (>6mm2), Fixed Copper (≤10mm2) Insulation X-HF-110
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu
1.5 25.0 24.0 20.0 16.0 12.0 31.0 24.0
Unenclosed spaced
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure

Selling & delivery Information

Nexans Fire Safety Offer ALSECURE® Fire Resistant Cables PVC-free Red List Free and Declare Labelled

 

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close