VERSOLEX 110 Flexible 50mm2 Cu Black

Description

Description

Standards

  • National
    AS/NZS 5000.1
  • 0.6/1kV cables,
  • Flexible X-HF-110 insulated to AS/NZS5000.1
  • TPE sheathed 
  • Copper flexible conductors.
  • Submersible up to 500m
  • Maximum operating temperature 110°C
  • PVC components meet Best Practice Guidelines for PVC in the built environment.

 

Also available in Low Smoke Zero Halogen (low fire hazard). See Envirolex - Low Fire Hazard

In systems intended to operate continuously at 110°C maximum operating temperature, Nexans Envirolex - Low Fire Hazard is recommended. Note that designing and operating a system continuously at maximum operating temperature is unlikely to be energy efficient over the life of the asset

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Black
Conductor flexibility
Class 5
Conductor material
Copper
Conductor shape
Circular
Insulation
X-HF-110
Outer sheath
TPE
Type of conductor
Copper
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
54.0 kg/100m
Cable length
- m
Conductor cross-section
50 mm²
Maximum diameter of wires
0.31 mm
Neutral conductor section (when smaller)
- mm²
Nominal overall diameter
14.1 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
0.523 Ohm/km
Inductive reactance at 50Hz - flat touching
0.105 Ohm/km
Inductive reactance at 50Hz - trefoil
0.09 Ohm/km
Insulation resistance at 20°C
250 MOhm.km
Max. DC resistance of the conductor at 20°C
0.384 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Maximum Pulling Tension
1 kN

Usage characteristics

Usage characteristics

Maximum operating temperature
110 °C
Minimum Bend Radius - During Installation (under Tension)
85 mm
Minimum Bend Radius - Installed
56 mm

Resources

Resources

VERSOLEX® 110 Flexible Single Core 110°C - Current carrying capacity table three phase (in Amps)

Insulation type: R-HF-110, R-E-110 OR X-HF-110 Maximum conductor temperature: 110°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
50.0 270.0 233.0 217.0 190.0 152.0 0.0 238.0 188.0 213.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual wiring enclosure

VERSOLEX® 110 Flexible Single Core 110°C - Current carrying capacity table single phase (in Amps)

Insulation type: R-HF-110, R-E-110 OR X-HF-110 Maximum conductor temperature: 110°C Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu Cu
50.0 279.0 263.0 218.0 207.0 165.0 0.0 284.0 215.0 237.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Enclosed, partially surrounded by thermal insulation
Enclosed, completely surrounded by thermal insulation
Buried direct
Underground Wiring Enclosure
Individual wiring enclosure

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close